WebOut of Wall Partitions for Fire Dampers (Static & Dynamic) and Fire Smoke Dampers Installation Instructions Important General Notes: When UL is referred to in this document, it represents UL/ULC. This installation instruction applies to Fire Dampers and Com-bination Fire/Smoke Dampers mounted outside the plane of an UL approved fire partition ... Webfloors be larger that the fire damper and sleeve assembly to allow for this expansion. Clearance required between the outside of fire damper sleeve assemblies and wall/floor openings are: - Galvanized steel fire dampers and sleeves: 1⁄ 8 inch (3 mm) per foot of damper width and height with minimum clearance ¼ inch (6 mm) and a maximum of 1½ ...
ocument 322 rille nstallation F F and FS Series - Greenheck-USA
WebLINE OF WALL DO NOT INSTALL SCREWS BETWEEN THESE LINES AROUND ENTIRE DAMPER Retaining Angles (see Section 4) Line of Wall Airflow Detail 1 DO NOT INSTALL SCREWS BETWEEN THESE LINES AROUND ENTIRE DAMPER Access door required on jackshaft side of damper. Refer to the latest edition of NFPA 90A. Jackshaft Actuator … WebBefore the static fire dampers are installed into the wall the mullions must first be anchored into the wall. The fire dampers may then be installed into the mullion assembly. To correctly attach the mullions to the wall, follow these steps: 1. Anchor wall mullion caps to wall using 1⁄ 4-20 x 5⁄ 16 in. long flat head steel bolts and 3⁄ how many hits in a joint
Smoke 1.5 Fire Smoke Dampers.Life Safety Dampers - GFSD-211 - Greenheck-USA
Webwall/floor by a minimum of 1 in. (25 mm)(see Figure 3). • For grille installation on fire damper up to 36 in. x 36 in. (914 mm x 914 mm) maximum, angle legs may be reversed and one leg inserted into the wall/floor opening providing the required clearance is maintained between angle leg fastener and the wall/floor opening. Note: Screws WebModel FD-110 is a narrowline static rated fire damper approved for use in walls, floors, and partitions with fire resistance rating less than 3 hours. This model carries a 11⁄ 2 hour UL fire damper label. UL 555 classifies static rated fire dampers for use in HVAC systems that are automatically shut down in the event of a fire. WebThe FSD-211 is a combination fire smoke damper with 3V-style blades. This model installs in walls, floors, or partitions and is rated for airflow and leakage in either direction. Pressure: Up to 6 in. wg Velocity: Up to 2,000 fpm Temperature: Up to 350°F 10-Day Fixed Lead Times on Select Configurations. Watch Now to Learn More! Certifications: how activating office 365 ms guides